Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
FKN12-12D/630-20 series air-blast load break switch (hereinafter referred to as FKRN12- 12D) and FKRN12-12D series air-blast load break switch and fuse combination apparatus are new series switchgear applies to three- phase electric distribution system of rated 12kV, acting as protecting and control apparatus for transformers, cable and over head wiring.
No. | Item | Unit | FKN12-12D/630 | FKRN12-12D/T125 |
1 | Rated voltage | kV | 12 | |
2 | Rated power frequency | Hz | 50 | |
3 | Rated current | A | 630 | 100 |
4 | Rated lightning impluse withstand voltage | kV | To ground and interphase, isolation break | |
5 | Power frequency withstand voltage | kV | To ground and interphase, isolation break | |
6 | Rated short-time withstand current | kA | 20(4s) | |
7 | Rated peak withstand current | kA | 50 | |
8 | Rated close current(peak) | kA | 50 | 50 |
9 | Rated short circuit breaking current(expected value) | kA | 31.5 | |
10 | Max.critical breaking current | A2S | Follow fuse characteristic curve | |
11 | Min. breaking current | kA | Follow fuse characteristic curve | |
12 | Rated transfer current | kA | 1.5 | |
13 | Max. breaking current(reference value) | kA | 1.8 | |
14 | Braking no-load transformer capcity | kva | 1250 | |
15 | Rated cable charging current | A | 10 | |
16 | Rated active load current breaking times | times | >100 | |
17 | Switch-off time of rated active load current | s | 20(2s) | >0.06 |
18 | Earthing switch thermal current | kA | 50 | 20(2s) |
19 | Earthing switch steady current(peak) | kA | 50 | |
20 | Motor operating power voltage | V | 100, 220 AC, DC |