| No. | Name | Unit | Data | ||||||
| 1 | Rated voltage | kV | 12 | ||||||
| 2 | Rated current | A | 630 | 1000 1250 | 1600 2000 2500 3150 | ||||
| 3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
| 4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
| 5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
| 6 | Rated short circuit making current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
| 7 | Switching operations of short circuit current | times | 50 | ||||||
| 8 | Rated operating sequence | O-0.3s-CO-180s-CO-180s-CO(40KA) | |||||||
| 9 | Mechanical endurance | times | 10000 | ||||||
| 10 | Rated breaking operations of the rated current | times | 20000 | ||||||
| 11 | Rated lighting impulse withstand voltage(full wave) | kV | 75 | ||||||
| 12 | 1 min. rated power frequency withstand voltage | kV | 42 | ||||||
| 13 | Contact stroke | mm | 9±1 | ||||||
| 14 | Over-travel of contacts | mm | 3.5±0.5 | ||||||
| 15 | Closing speed | m/s | 0.4∼0.8 | ||||||
| 16 | Opening speed | m/s | 0.9∼1.2 | ||||||
| 17 | Contact bouncing duration at closing operation | ms | ≤2 | ||||||
| 18 | Simultaneity of three phase closing operation | ms | ≤2 | ||||||
| 19 | Closing time | ms | 30∼70 | ||||||
| 20 | Opening time | m/s | 20∼50 | ||||||
| 21 | Distance between phases | mm | 150, 210, 275 | ||||||
| 22 | D.C component | 50% | |||||||
Note:
1. No.11&12 are provided when needed.
2. Switchgear should be with cold wind when the rated current is 4000A.
Ambient condition
1.Ambient temperature:-10ºC-+40ºC
2.Relative humidity:The average humidity of a day should be no more than 95%. The average humidity of a month should be no more than 90%.
3.Earthquake intensity: not exceed 8 degrees.
5.The height above sea level:≤1000 m (Except special requirements)
6.It should be installed in the places without fire, explosion, serious filth, and chemical erosion and violent vibration.
![]() |