Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 720/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GW -12/24/40.5-630-20(25) outdoor AC high voltage disconnect switch (disconnect switch for short) is used to open and close circuit with voltage but no-load 50/60Hz,12/24/40.5kV power system, the anti-pollution type can be used in the serious pollution area. Three pole linkage, good synchronous performance. It accords with standards of IEC62271-103:High voltage switches.
Technical parameter
No.
|
Item
|
Unit
|
Data
|
||||
1 | Rated voltage | kV | 12/24/40.5 | ||||
2
|
Rated current
|
A
|
630/1000/1250
|
||||
3
|
Rated power frequency
|
Hz
|
50/60
|
||||
4
|
Rated peak withstand current
|
kA
|
50/63
|
||||
5
|
Rated short-time withstand current
|
kA
|
20/25
|
||||
6
|
Rated short-time withstand current duration
|
s
|
4
|
||||
7
|
Main loop resistance
|
μΩ
|
12kV≤80
|
24kV≤90
|
40.5kV≤100
|
||
8
|
1min(dry)power frequency withstand voltage
|
phase to phase
phase to earth
across open contacts
|
kV
|
42/48
|
50/60
|
95/115
|
|
9
|
1min(wet)power frequency withstand voltage
|
34
|
50
|
85
|
|||
10
|
lightning impulse wuthstand voltage(peak)
|
75/85
|
125/145
|
185/215
|
|||
11
|
Mechanical life
|
Times
|
2000
|
|