Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Summary:
FLN36-12D/T630-25 indoor AC high voltage SF6 load switch and FLRN36-12D/T1250-31.5 indoor AC high voltage SF6 load switch fuse combination apparatus is suitable for protecting the line of 10kV Electric Power Load Control System in three-phase 50Hz ring networks or terminal power supply and industrial electrical equipment.
Features:
- Capable of breaking any current reaching rated short circuit
- Suitable for ring network units, box type substations, and more
- Ideal for urban residential areas, industrial and mining enterprises, airports, hospitals, and more
Ambient Conditions:
1. Altitude: ≤2000m
2. Ambient Temperature: -40°C to +40°C
3. Earthquake Intensity: ≤8 degree
4. Relative Humidity: Daily averages ≤95%, Monthly average ≤90%
Company: Yueqing Liyond Electric Co., Ltd.
Item | Unit | Data | |||
FLN36-12D/T630-25 | FLRN36-12D/T1250-31.5 | ||||
Rated voltage | kV | 12 | |||
Rated frequency | Hz | 50 | |||
Rated current | A | 630 | 1250 | ||
Rated active load breaking current | 630 | ||||
Rated closed loop dropout current | 630 | ||||
Rated transfer current | 1700 | ||||
Lightning impulse withstand voltage(peak) | kV | phase to earth, between phase 75, fracture 85 | |||
1 min power frequency withstand voltage | phase to earth, between phase 42, fracture 48 | ||||
Rated short-time withstand current(2s) | kA | 25 | |||
Rated peak withstand current | 63 | ||||
Rated short-circuit closing current(peak) | 63 | 80(expected) | |||
Fuse type | S LAJ-12 | ||||
Output energy of impactor | J | 1+0.5 | |||
Mechanical life | Load switch | times | 5000 | ||
Earth switch | 2000 |