Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
FN7-12DR is used in tri-phase AC power network of AC 50Hz, rated voltage 12kv for breaking load current and controling short circuit current.
FN7(C)-12 type H.V. load switch and fuse box is based on the FN7-12 series H.V. load switch with operating mechanism, making the installation more simpler.
Classification | Full type | DS Earth switch at the wire-in end | DX Earth switch at the wire-out end | L Interlock device | R Fuse box | RA String fuse box | F Off device by motor |
Without tripper | FN7-12 | - | - | - | - | - | - |
FN7-12DSL | △ | - | △ | - | - | - | |
FN7-12DXL | - | △ | △ | - | - | - | |
FN7-12R | - | - | - | △ | - | - | |
FN7-12DSLR | △ | - | △ | △ | - | - | |
FN7-12DXLR | - | △ | △ | △ | - | - | |
With striking tipper | FN7- 12RAF | - | - | - | - | △ | △ |
FN7-12DSLRAF | △ | - | △ | - | △ | △ | |
FN7-12DXLRAF | - | △ | △ | - | △ | △ |
Rated voltage | Max.voltage | Rated current | Power frequency withstand voltage | 4S heat-stabling current(value) | Machine stabling current(peak) | Short-circuit corntrlling current | Rated switch-off current | Rated transfer current |
12 | 12 | 400 | 42/48 | 12.5 | 31.5 | 31.5 | 400 | 1000 |
630 | 75/85 | 20 | 50 | 50 | 630 | 1000 |
Model | Rated voltage(kV) | Rated current(A) | Fuse body rated current |
SDLA*J | 12 | 40 | 6.3, 10, 16, 20, 31.5, 40 |
SFLA*J | 12 | 100 | 50, 63, 71, 80, 100 |
SKLA*J | 12 | 125 | 125 |