Model VS1 series of circuit breakers assembly are mainly used in the rated voltage12-24kv, the rated short circuit breaking current 20 and 50KA, and the rated current 630-5000A for the power distribution users.
The mechanical endurance is 20000 operating and 50 operating full capacity breaking ability at small current. It is suitable for the application with frequent operation and it features free of maintenance and few service.It could be used with Model KYN28A(GZS1) metal-enclosed switchgear and other fixed cabinet or handcart cabinet.
Technical parameters :
No. | Name | Unit | Data | ||||||
1 | Rated voltage | kV | 12 | ||||||
2 | Rated current | A | 630 | 1000 1250 | 1600 2000 2500 3150 | ||||
3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
6 | Rated short circuit making current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
7 | Switching operations of short circuit current | times | 50 | ||||||
8 | Rated operating sequence | O-0.3s-CO-180s-CO-180s-CO(40KA) | |||||||
9 | Mechanical endurance | times | 10000 | ||||||
10 | Rated breaking operations of the rated current | times | 20000 | ||||||
11 | Rated lighting impulse withstand voltage(full wave) | kV | 75 | ||||||
12 | 1 min. rated power frequency withstand voltage | kV | 42 | ||||||
13 | Contact stroke | mm | 9±1 | ||||||
14 | Over-travel of contacts | mm | 3.5±0.5 | ||||||
15 | Closing speed | m/s | 0.4∼0.8 | ||||||
16 | Opening speed | m/s | 0.9∼1.2 | ||||||
17 | Contact bouncing duration at closing operation | ms | ≤2 | ||||||
18 | Simultaneity of three phase closing operation | ms | ≤2 | ||||||
19 | Closing time | ms | 30∼70 | ||||||
20 | Opening time | m/s | 20∼50 | ||||||
21 | Distance between phases | mm | 150, 210, 275 | ||||||
22 | D.C component | 50% |
Note:
1. No.11&12 are provided when needed.
2. Switchgear should be with cold wind when the rated current is 4000A.
Ambient condition
1.Ambient temperature:-10ºC-+40ºC
2.Relative humidity:The average humidity of a day should be no more than 95%. The average humidity of a month should be no more than 90%.
3.Earthquake intensity: not exceed 8 degrees.
5.The height above sea level:≤1000 m (Except special requirements)
6.It should be installed in the places without fire, explosion, serious filth, and chemical erosion and violent vibration.