VSG indoor high-voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is an indoor switchgear for 12kV power system. It is used as a protection and control unit for power grid equipment and industrial and mining enterprises. And occasions of frequent operation and multiple interruption of short-circuit current. The product adopts a new type of circuit breaker operating mechanism. The primary part of the VSG can use international brand solid sealing poles to seal the vacuum interrupter and the main circuit parts into a whole, protecting the arc quenching chamber from collision, dust and condensation. Strong environmental adaptability, greatly reducing the cost of operation and maintenance, truly realizing the product is partly maintenance-free, and the operating mechanism is less maintenance; the integrated design of the operating mechanism and the circuit breaker body, after type test verification, has E2 level electrical life, M2 class mechanical life can be used as a fixed installation unit, or can be equipped with a special propulsion mechanism to form a handcart unit. Among them, fixed circuit breakers can be added with corresponding interlocks to meet the requirements of XGN2, GG1A, GGX and other fixed cabinets need.
Applying Ambient Conditions
1. Ambient temperature: -10ºC-+40ºC
2. Ambient humidity: the average humidity of a day should be no more than 95%; the average humidity of a month should be no more than 90%;
3. Earthquake intensity: not exceed 8 degrees
4. Saturated vapor pressure: average pressure of a day should be no more than2. 2kPa,the average pressure of a month should be no more than 1.8kPa;
5. The height above sea level: 1000m(not including special requirements)
6. It should be installed in the places without fire, explosion, serious filth, chemical corrosion and violent VS1 ration.
Technical datas
No. | Name | Unit | Data | ||||||
1 | Rated voltage | kV | 12 | ||||||
2 | Rated current | A | 630 | 1000 1250 | 1600 2000 2500 3150 | ||||
3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
6 | Rated short circuit making current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
7 | Switching operations of short circuit current | times | 50 | ||||||
8 | Rated operating sequence | O-0.3s-CO-180s-CO-180s-CO(40KA) | |||||||
9 | Mechanical endurance | times | 10000 | ||||||
10 | Rated breaking operations of the rated current | times | 20000 | ||||||
11 | Rated lighting impulse withstand voltage(full wave) | kV | 75 | ||||||
12 | 1 min. rated power frequency withstand voltage | kV | 42 | ||||||
13 | Contact stroke | mm | 9±1 | ||||||
14 | Over-travel of contacts | mm | 3.5±0.5 | ||||||
15 | Closing speed | m/s | 0.4∼0.8 | ||||||
16 | Opening speed | m/s | 0.9∼1.2 | ||||||
17 | Contact bouncing duration at closing operation | ms | ≤2 | ||||||
18 | Simultaneity of three phase closing operation | ms | ≤2 | ||||||
19 | Closing time | ms | 30∼70 | ||||||
20 | Opening time | m/s | 20∼50 | ||||||
21 | Distance between phases | mm | 150, 210, 275 | ||||||
22 | D.C component | 50% |
FAQ
Q: Could I have prices of your products?
A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours.
Q: Can I get a sample before the bulk order?
A: Yes, we welcome sample order to test and check quality.Mixed samples are acceptable.
Q: Can we print our logo/ company name on products?
A: Yes, of course, we accept OEM, then need you to provide brand authorization to us
Q:Do you accept product customization?
A:Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation
Q: What is the lead time?
A: The lead time depends on the quantities ordered, generally within 7-20 days after receiving the payment.
Q: What is your Trade Terms?
A: We accept EXW, FOB, CIF, FCA, etc.
Q: What is your payment method?
A: We accept T/T, Western Union, Paypal, irrevocable L/C at sight, etc
Q: Do you inspect the finished products?
A: Yes, each step of production and finished products will be came out inspection by QC department before shipping. And we will provide goods inspection reports for your reference before shipment
Q: How to solve the quality problems after sales?
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days.