| Customization: | Available |
|---|---|
| Certification: | ISO9001 |
| Shell Material: | Stainless Steel |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| Unit code | Significance |
| C | Standard single bushing load switch unit |
| F | Load switch-fuse combination unit |
| V | Circuit breaker unit |
| D | Cable inline unit (without switch) |
| + | Busbar side bushing |
| - | Busbar top bushing |
| SL | Bus coupling unit |
| M | Metering unit |
| PT | PT unit |
| 1K2(4) | Load switch unit with double bushing outlet |
| Model | Width | Deep | High | a | b | C | Weight(kg) |
| C+ | 371 | 751 | 1336 | 1146 | 710 | 510 | 136 |
| 1k2(4) | 426 | 820 | 480 | 420 | 420 | 510 | 182 |
| 2C+ | 696 | 751 | 1336 | 1146 | 710 | 510 | 206 |
| 3C | 1021 | 751 | 1336 | 1146 | 710 | 510 | 300 |
| 4C | 1346 | 751 | 1336 | 1146 | 710 | 510 | 390 |
| 5C | 1671 | 751 | 1336 | 1146 | 710 | 510 | 486 |
| F | 371 | 751 | 1336 | 1146 | 710 | 510 | 164 |
| V | 371 | 751 | 1336 | 1146 | 710 | 460 | 230 |
| Item | Unit | Load switch unit | Combined electrical unit | Circuit breaker unit | |
| Rated voltage | KV | 12/24 | 12/24 | 12/24 | |
| Rated frequency | Hz | 50 | 50 | 50 | |
| Rated current | A | 630 | depends on fuse current rating | 630 | |
| Rated insulation level | Power frequency withstand voltage (interphase and relative ground) | KV | 42/65 | 42/65 | 42/65 |
| Power frequency withstand voltage (between fractures) | 48/79 | 48/79 | 48/79 | ||
| Power frequency withstand voltage(control and auiliary circuit) | 2/2 | 2/2 | 2/2 | ||
| Lightning impulse withstand voltage(interphase and relative ground) | 75/125 | 75/125 | 75/125 | ||
| Lightning impulse withstand voltage (between fractures) | 85/145 | 85/145 | 85/145 | ||
| Zero gauge pressure test | - | pass | pass | pass | |
| Rated short-time withstand current | KA | 20/4s 20/3s | - | 20/4s 20/4s | |
| Rated peak withstand current | KA | 63 | - | 63 | |
| Rated short- circuit making current | KA | 50/63 | limited to high voltge fuese | 50 | |
| Rated short- circuit breaking current | KA | - | limited to high voltge fuese | 20/20 | |
| Rated transfer current | A | - | 1750/1400 | - | |
| Rated active load breaking current | A | 630 | - | - | |
| Rated closed-loop breaking current | A | 630 | - | 630 | |
| Mechanical life |
Load switch/ circuit breaker | time | 5000 | 5000 | 10000 |
| Isolation/earth switch | 5000 | 5000 | 5000 | ||
| Loop resistance | μΩ | ≤120 | - | ≤120 | |
| Inflation pressure |
Rated inflation pressure (absolute pressure) | bar | 1.3 | 1.3 | 1.3 |
| Minimum inflation pressure (absolute pressure) | 1.2 | 1.2 | 1.2 | ||
| Annual gas leakage rate | % | ≤0.02 | ≤0.02 | ≤0.02 | |