Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZW32-24 outdoor AC high-voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is rated voltage of 24kV, 50Hz three-phase AC outdoor power distribution equipment. It is mainly used to open and close the load current, overload current and short circuit current in the power system. Overload current and short-circuit current. Suitable for substations and industrial and mining enterprises in the distribution system for protection and control purposes, more It is suitable for the rural grid and the place of frequent operation.
Structure schematic
Main technical parameters of circuit breaker
No. | Item | Unit | Data |
1 | Rated voltage | kV | 24 |
2 | rated frequency | Hz | 50 |
3 | rated current | A | 630/1250/1600 |
4 | Rated short-circuit breaking current | kA | 20/25/31.5 |
5 | Rated peak withstand current (peak) | kA | 50/63/80 |
6 | Rated short-time withstand current/duration | kA/s | 25/4 |
7 | Rated short-circuit making current (peak value) | kA | 50/63/80 |
8 | Nominal sequence of operations. | 0-0.3s-CO-180s-CO | |
9 | Mechanical life | times | 10000 |
10 | Rated current breaking times | times | 10000 |
11 | Rated short-circuit breaking current breaking times | times | 20 |
12 | 1min power frequency withstand voltage; (wet) phase to phase, ground / fracture (dry) phase to phase, ground / fracture |
kV |
50/60 60/65 |
13 | Lightning impulse withstand voltage (peak value) Phase-to-phase, ground/fracture |
kV | 95/125 |
14 | Secondary circuit 1 min power frequency withstand voltage | V | 2000 |
Normal use conditions
1. Altitude 1000m;
2. The ambient air temperature is 45°C~+65°C; the daily temperature difference is 25°C;
3. The wind speed is not greater than 35m/s;
4. The earthquake intensity does not exceed 8 degrees;
5. Pollution level: Level IV;
6. Installation place: No flammable, dry explosion hazard, chemical corrosion place.
Application
Order instructions
When ordering, please specify the product type, name, quantity, rated current, rated short-circuit breaking current, current ratio of the current transformer, operation mode and operating voltage, etc.