• Low Voltage 1140V Vacuum Circuit Breaker for Mining
  • Low Voltage 1140V Vacuum Circuit Breaker for Mining
  • Low Voltage 1140V Vacuum Circuit Breaker for Mining
  • Low Voltage 1140V Vacuum Circuit Breaker for Mining
  • Low Voltage 1140V Vacuum Circuit Breaker for Mining

Low Voltage 1140V Vacuum Circuit Breaker for Mining

Breaking Capacity: High Voltage Circuit Breakers
Operation: Energy-storage Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Vacuum
Installation: Fixed
Structure: Vcb
Customization:
Diamond Member Since 2009

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
ZK1-1.14KV/630A
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, OVP(Overvoltage Protection), RCCB, Do as Your Request
Certification
ISO9001-2000, CE
Rated Voltage
1.14 Kv
Rated Frequency
50Hz
Rated Current
630A
Phase Distance
94mm
Transport Package
Wooden Case
Specification
steel, expoxy resin
Trademark
LIYOND
Origin
China
Production Capacity
3000/Month

Product Description

Low Voltage 1140V Vacuum Circuit Breaker for Mining
Low voltage 1140V vacuum circuit breaker for mining
Summary
Our ZK1 low voltage vacuum circuit breaker is suitable for AC 50Hz, rated voltage of 1140V and below, and rated current of 630A and below, as the main switch and branch switch of the power supply system.
It can also be used for infrequent starting of large-capacity motors. And it is suitable for various protection devices to form various distribution switches, especially suitable for forming explosion-proof vacuum feeder switches in coal mines.

Applying ambient conditions
1. Ambient temperature: -5°C~+40°C;
2. Atmospheric conditions: When the temperature is +40°C, the relative humidity is not more than 50%;
3. Installation conditions: vertical installation, the inclination does not exceed 15°;
4. Pollution degree three: installation category main circuit III, control circuit II;
5. The height above sea level: <2000 m (Except special requirements);
 

 

Technical datas

 

Item
Unit
Data
Rated current
A
630
Rated voltage
kV
1.14
Limited Making Capacity
kA
12.5
Inherent Opening Time
ms
≤ 30
Closing Time
ms
≤ 100
Closing Bounce Time
ms
≤ 2
Mechanica life
times
20000
Electrical life
times
3000
Control voltage
V(AC)
220
Under Voltage, Shunt Release DC Supply
V
48
Closing power(W transient) W
W
2782
Closing power
W
48
Under-voltage power
W
5
Auxiliary switch
3NO, 3NC
Auxiliary contact capacity
Ue:AC380V Ie: 10A
Low Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for Mining
Low Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for Mining


Low Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for MiningLow Voltage 1140V Vacuum Circuit Breaker for MiningFAQ

Q: Could I have prices of your products?

A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours.

 

Q: Can I get a sample before the bulk order?

A: Yes, we welcome sample order to test and check quality.Mixed samples are acceptable.

 

Q: Can we print our logo/ company name on products?

A: Yes, of course, we accept OEM, then need you to provide brand authorization to us

 

Q:Do you accept product customization?

A:Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation


Q: What is the lead time? 
A: The lead time depends on the quantities ordered, generally within 7-20 days after receiving the payment. 

 

Q: What is your Trade Terms? 
A: We accept EXW, FOB, CIF, FCA, etc

 

Q: What is your payment method?  
A: We accept T/T, Western Union, Paypalirrevocable L/C at sight, etc 

 

Q: Do you inspect the finished products?

A: Yes, each step of production and finished products will be came out inspection by QC department before shipping. And we will provide goods inspection reports for your reference before shipment


Q: How to solve the quality problems after sales? 
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days. 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2009

Suppliers with verified business licenses

Trading Company
Number of Employees
18
Year of Establishment
2011-04-07