Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker

Product Details
Customization: Available
Breaking Capacity: High Voltage Circuit Breakers
Operation: Energy-storage Type
Diamond Member Since 2009

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
18
Year of Establishment
2011-04-07
  • Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
  • Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
  • Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
  • Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
  • Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
Find Similar Products

Basic Info.

Model NO.
VSM-12
Arc-extinguishing Medium
Vacuum
Installation
Insert
Structure
Vcb
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), RCCB, Do as Your Request
Certification
ISO9001-2000, CE
Rated Voltage
12kv
Rated Frequency
50/60Hz
Rated Current
630A/1250A/1600A/2000A
Phase Distance
150mm/210mm
Transport Package
Wooden Case
Specification
steel, expoxy resin
Trademark
LIYOND
Origin
China
Production Capacity
3000/Month

Product Description

Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
VSM-12 12KV handcart type permanent magnet mechanism Indoor vacuum circuit breaker

Summary

The permanent magnet operating mechanism and the vacuum interrupter of the 12/M vacuum circuit breaker adopt front and rear arrangement,. The main conductive circuit is a floor-standing structure. The upper and lower outlet seats and the vacuum interrupter are installed in a tubular insulating cylinder. Inside. The insulating cylinder is made of epoxy resin by APG process.This structure can prevent dust accumulation on the surface of the vacuum arcing chamber and prevent it from being damaged by external factors. It can ensure that the product still has good insulation performance in the humid and hot environment and serious pollution.

 Main technical parameters

Table 1.  Technical parameters

No Item Unit Specification
1 Rated Voltage kV 12
2 Rated Current A 630 1000,1250 1600,2000,2500,3150
3 Rated short circuit breaking current kA 20 25 20 25 31.5 31.5 40
4 Rated peak withstand current kA 50 63 50 63 80 80 100
5 Rated short-time withstand current kA 20 25 20 25 31.5 31.5 40
6 Rated short circuit closing current kA 25 63 25 63 80 80 100
7 Breaking times of short circuit current  times 50 30
8 Rated operating sequence   O-0.3s-CO-180s-CO,O-180s-CO-180s-CO(40kA)
9 Mechanical life times 30000(small current) 20000(heavy current)
10 Breaking times of rated current times 30000(small current) 20000(heavy current)
11 Rated lightning impulse withstand voltage (full wave) kV 75
12 Rated short-time power frequency withstand voltage kV/min 42

 Table 2.Parameters of circuit breakers with capacitors

No Item Unit Specification
1 Travel of the contact mm 11±1
2 Over-travel of the contact mm 3.5±0.5
3 Closing speed m/s 0.6±0.2
4 Opening speed m/s 1.1±0.3
5 Contact closing bounce time ms ≤2,≤3(40kA)
6 Three-phase contact closing and opening synchronization ms ≤2
7 Closing time ms ≤22
8 Opening time ms ≤20
9 Energy storage loop supply voltage V 110,220
10 Energy storage loop current A ≤0.5(Before the capacitor is full),≤0.01(After the capacitor is full)
11 Energy storage time s ≤10,First charge time≥30
12 Closing control voltage V 110,220
13 Opening control voltage V 110,220
14 Closing control current A 0.2
15 Opening control current A 0.2
16 Main loop resistance μΩ ≤60(630A),≤45(1250A),≤30(2000A above)
17 Phase distance mm 210,275(40kA)

Table 3.Parameters of circuit breakers with capacitors

No Item Unit Specification
1 Travel of the contact mm 11±1
2 Over-travel of the contact mm 3.5±0.5
3 Closing speed m/s 0.6±0.2
4 Opening speed m/s 1.1±0.3
5 Contact closing bounce time ms ≤2,≤3(40kA)
6 Three-phase contact closing and opening synchronization ms ≤2
7 Closing time ms ≤75
8 Opening time ms ≤65
9 Energy storage loop supply voltage V DC220-DC240V(From DC screen)
10 Energy storage circuit closing current A 35<I<55(Small current)
11 Energy storage circuit opening current A 10<I<20
12 Energy storage circuit closing time ms ≤60
13 Energy storage circuit opening time ms ≤25
14 Closing control voltage V 110,220
15 Opening control voltage V 110,220
16 Closing control current A 0.2
17 Opening control current A 0.2
18 Main loop resistance μΩ ≤60(630A),≤45(1250A),≤30(2000A the above)
19 Phase distance mm 210,275(40kA)

Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker
Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker

Vsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit BreakerVsm-12 12kv Handcart Type Permanent Magnet Mechanism Indoor Vacuum Circuit Breaker





FAQ

Q: Could I have prices of your products?

A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours.

 

Q: Can I get a sample before the bulk order?

A: Yes, we welcome sample order to test and check quality.Mixed samples are acceptable.

 

Q: Can we print our logo/ company name on products?

A: Yes, of course, we accept OEM, then need you to provide brand authorization to us

 

Q:Do you accept product customization?

A:Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation


Q: What is the lead time? 
A: The lead time depends on the quantities ordered, generally within 7-20 days after receiving the payment. 

 

Q: What is your Trade Terms? 
A: We accept EXW, FOB, CIF, FCA, etc

 

Q: What is your payment method?  
A: We accept T/T, Western Union, Paypalirrevocable L/C at sight, etc 

 

Q: Do you inspect the finished products?

A: Yes, each step of production and finished products will be came out inspection by QC department before shipping. And we will provide goods inspection reports for your reference before shipment


Q: How to solve the quality problems after sales? 
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days. 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now