Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Stainless Steel |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
HXGN15-12/24 series of products is consist of standard functional units, which are completed by the factory processing, using technologically advanced FLN36-12/24 load break switch, using superior performance of SF6 gas as the arc extinction insulating medium. The cabinet has advantages of small volume, reasonable and compact, convenient installation, simple operation, safe and stable operation,which has been widely recognized in the 10KV or 24KV power supply system.
Load switch and earthing switch adopts obstacles chain, between of grounding switch and the door adopts mandatory chain. Follow these steps can realize the automatic chain: shut the doors, open the grounding switch, close load switch, the separate operation mode effectively avoid misoperation.
S/N |
Item |
Unit |
parameters |
|
1 |
Rated voltage |
KV |
12, 24, 33,40.5KV |
|
2 |
Rated current |
A |
630 |
|
3 |
Rated frequency |
Hz |
50 |
|
4 |
Rated short time withstand current |
KA |
20 |
|
5 |
Rated short circuit duration |
S |
4 |
|
6 |
Rated withstand current (peak) |
KA |
50 |
|
7 |
Rated short circuit duration of grounding switch |
S |
4 |
|
8 |
Rated short withstand current (peak) of grounding switch |
KA |
50 |
|
9 |
Rated insulation level |
1min power frequency withstand voltage (effective value) |
KV |
(phase-phase, phase-earth)42; (fracture) 48 |
Lightning impulse withstand voltage (peak) |
KV |
phase-phase, phase-earth)75; (fracture) 85 |
||
10 |
Rated SF6 pressure (20°C gage pressure0 |
Mpa |
0.04 |
|
11 |
SF6 leakage rate per year |
|
1% |
|
12 |
Protection degree |
|
IP3* |