Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Aluminum Alloy |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Unit code | Significance |
C | Standard single bushing load switch unit |
F | Load switch-fuse combination unit |
V | Circuit breaker unit |
D | Cable inline unit (without switch) |
+ | Busbar side bushing |
- | Busbar top bushing |
SL | Bus coupling unit |
M | Metering unit |
PT | PT unit |
1K2(4) | Load switch unit with double bushing outlet |
Model | Width | Deep | High | a | b | C | Weight(kg) |
C+ | 371 | 751 | 1336 | 1146 | 710 | 510 | 136 |
1k2(4) | 426 | 820 | 480 | 420 | 420 | 510 | 182 |
2C+ | 696 | 751 | 1336 | 1146 | 710 | 510 | 206 |
3C | 1021 | 751 | 1336 | 1146 | 710 | 510 | 300 |
4C | 1346 | 751 | 1336 | 1146 | 710 | 510 | 390 |
5C | 1671 | 751 | 1336 | 1146 | 710 | 510 | 486 |
F | 371 | 751 | 1336 | 1146 | 710 | 510 | 164 |
V | 371 | 751 | 1336 | 1146 | 710 | 460 | 230 |
Item | Unit | Load switch unit | Combined electrical unit | Circuit breaker unit | |
Rated voltage | KV | 12/24 | 12/24 | 12/24 | |
Rated frequency | Hz | 50 | 50 | 50 | |
Rated current | A | 630 | depends on fuse current rating | 630 | |
Rated insulation level | Power frequency withstand voltage (interphase and relative ground) | KV | 42/65 | 42/65 | 42/65 |
Power frequency withstand voltage (between fractures) | 48/79 | 48/79 | 48/79 | ||
Power frequency withstand voltage(control and auiliary circuit) | 2/2 | 2/2 | 2/2 | ||
Lightning impulse withstand voltage(interphase and relative ground) | 75/125 | 75/125 | 75/125 | ||
Lightning impulse withstand voltage (between fractures) | 85/145 | 85/145 | 85/145 | ||
Zero gauge pressure test | - | pass | pass | pass | |
Rated short-time withstand current | KA | 20/4s 20/3s | - | 20/4s 20/4s | |
Rated peak withstand current | KA | 63 | - | 63 | |
Rated short- circuit making current | KA | 50/63 | limited to high voltge fuese | 50 | |
Rated short- circuit breaking current | KA | - | limited to high voltge fuese | 20/20 | |
Rated transfer current | A | - | 1750/1400 | - | |
Rated active load breaking current | A | 630 | - | - | |
Rated closed-loop breaking current | A | 630 | - | 630 | |
Mechanical life |
Load switch/ circuit breaker | time | 5000 | 5000 | 10000 |
Isolation/earth switch | 5000 | 5000 | 5000 | ||
Loop resistance | μΩ | ≤120 | - | ≤120 | |
Inflation pressure |
Rated inflation pressure (absolute pressure) | bar | 1.3 | 1.3 | 1.3 |
Minimum inflation pressure (absolute pressure) | 1.2 | 1.2 | 1.2 | ||
Annual gas leakage rate | % | ≤0.02 | ≤0.02 | ≤0.02 |